DSE501K
1)INTRODUCTION:
DSE501K is a Manual Engine Control Module, which has been designed to manually control the engine via a key switch on the front panel. The module is used to start and stop the engine, indicating fault conditions; automatically shutting down the engine and indicating the engine failure by LED giving true first up fault annunciation.
2) SPECIFICATION:
A. DC Supply----9~33V continuous.
B. Alternator Input Range----15~305V AC RMS
C. Alternator Input Frequency---- 50~60Hz at rated engine speed.
D. Magnetic Input Range----0.5V~+/-80V
E. Magnetic Input Frequency----2300Hz~6000Hz
F. Start Relay Output----16 Amp DC at supply voltage
G. Run Relay Output----16 Amp DC at supply voltage
H. Alarm Output----1Amp DC at supply voltage
I. Operating Temperature Range----- -30~70celsius
3)TECHNICAL DATA:
Power Supply | 9 to 33 Vdc Continuous |
Cranking Dropouts: | Able to survive voltage dips during cranking. Without The need for internal batteries. |
Alternator Input Range | 15 - 305 V AC RMS |
Alternator Input Frequency: | 50 - 60 Hz at rated engine speed |
Magnetic Input Range | 0.5 V to +/- 80 V |
Magnetic Input Frequency | 2300Hz to 6000 Hz at rated engine speed |
Start Relay Output: | 16 Amp DC at supply voltage |
Run Relay Output: | 16 Amp DC at supply voltage |
Alarm Output | 1 Amp DC at supply voltage |
Operating Temperature Range: | -30 to +70°C |
DSE3110
The DSE3110 can be utilised as a Manual or Auto Start Module for single gen-set applications or engine only applications. The module has been designed to work with electronic and non-electronic engines, providing advanced engine monitoring and protection features.
The DSE3110 includes a back-lit icon LCD display which clearly shows the status of the engine at all times.
The module has been designed to combine a maximum of 16 generators and 16mains (utility)
supplies up to a maximum of 20 in one system, e.g. 16 generators and 4mains (utility) supplies (DSE5560 required to synchronise with the mains).
DSE5110
The module DSE5110 is used to automatically start and stop the engine,indicating the operational status and faultconditions by means of an LCD display and a flashing LED on the front panel.
Power Supply | 8 to 35 Vdc Continuous |
Cranking Dropouts: | Able to survive 0 V for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5V. |
Max Current | Operating 425mA at 12 V & 215mA at 24 V; Standby 250 mA at 12 V & 125 mA at 24 V. |
Start Relay Output: | 16 Amp DC at supply voltage. |
Fuel Relay Output: | 16 Amp DC at supply voltage. |
Auxiliary Relay Outputs: | 5 Amp DC at supply voltage. |
Charge Fail / ExcitationRange | 0 V to 35 V |
Maximum operating current | 320ma at 12V, 215ma at 24v |
Maximum operating current | 175ma at 12V, 95ma at 24v |
AlternatorInputRange: | 15V(L-N) to 333V AC (L- N) absolute maximum |
Alternator Input Frequency: | 50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N) |
Magnetic Pick-upVoltageInputRange: | +/- 0.5 V to 70 V Peak |
Magnetic Input Frequency: | 10,000 Hz (max) at rated engine speed |
MAINS (UTILITY) SENSING INPUT RANGE | (DSE5220 only) 15V (L-N) to 333V AC (L-N) absolute maximum |
MAINS(UTILITY)SENSINGINPUTFREQUENCY | (DSE5220 only) 50-60 Hz |
MAINS (UTILITY) & GENERATOR LOADING RELAY OUTPUT | (DSE5220 only) 8A AC 250V |
Generator loading Relay Output: | 8 Amp AC 250V. |
Mains loading Relay Output: | 8 Amp AC 250V |
Panel Cutout: | 220mm x 160mm ( 8.7" x 6.3") |
DSE5120
1.Introduction
*The Model 5120 is an Automatic Mains Failure Module which has been designed to allow the OEM to meet demand
for increased capability within the generator industry.
*The module has been primarily designed to monitor the incoming mains supply.
*Should the mains supply fall below a configurable limit, the generator will be automatically started and the load
transferred.
2.Technical data:
Power Supply | 8 to 35 Vdc Continuous |
Cranking Dropouts: | Able to survive 0 V for 50mS, providing supply was at least 10V before dropout and supply recovers to 5V without the need for internal batteries. |
Max Current | Operating 320mA at 12V, 215mA at 24V; Standby 175mA at 12V, 95mA at 24V |
Start Relay Output: | 16 Amp DC at supply voltage. |
Fuel Relay Output: | 16 Amp DC at supply voltage. |
Auxiliary Relay Outputs: | 5 Amp DC at supply voltage. |
Charge Fail / Excitation Range | 0 V to 35 V |
Alternator Input Range: | 15V(ph-N) to 300V(ph-N) 3 Phase 4wire AC (+20%) |
Alternator Input Frequency: | 50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N) |
Mains Supply Input Range: | 15V(ph-N) to 300(ph-N) 3 Phase 4wire AC (+20%) |
Mains Supply Input Frequency: | 50 - 60 Hz at rated engine speed (Minimum: 15V AC Ph-N) |
Magnetic Pick-up Voltage Input Range: | +/- 0.5 V to 70 V Peak |
Magnetic Input Frequency: | 10,000 Hz (max) at rated engine speed |
Operating Temperature Range: | -30 to +70°C |
Panel Cutout: | 220mm x 160mm ( 8.7" x 6.3" |
We Populace Electronic Co., Ltd is one of the leading manufactures of AVR and other generator parts in China. And we have many years'experience in this particular line of business.
Our main product have GAVR-8A, GAVR-12A, GAVR-15A; Leroy somer series R448, R438, R250, R449, R230; Stamdford series SX440, SX460, MX321, MX341, AS440; Marathon series SE350; Gasoline AVR 2KW and 5KW; Brush AVR and so on.
We also have other generator parts, such as frequency changer, engine governor, controller, battery charger and other electronic products.
Sincerely welcome merchants at home and abroad to visit us to cooperate and develop together.